Huawei ECC800 User Manual page 183

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Context
Procedure
Step 1 Set functions of the infrared remote control module on the WebUI.
1.
2.
3.
4.
5.
6.
7.
8.
Step 2 (Optional) Set functions on the infrared remote control module.
1.
2.
3.
Issue 06 (2020-04-22)
The infrared remote control module supports self-learning and can remotely control the
startup of the civil smart cooling product.
The infrared remote control module can be in infrared learning state and control code
sending state. After power-on, the device is in normal operating mode by default.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Linkage Control, set Enable linkage control to Yes, and
click Submit. Set Automatic air conditioner startup to On.
Choose Monitoring > System > Infrared Remote Control Module.
On the Controls tab page, choose Learning the startup instruction, and click Submit.
Direct the remote control of the smart cooling product to the infrared receiving place on
the infrared remote control module, and press the power button once.
If you do not press the button within 20s, the remote control of the smart cooling product will exit the
learning mode due to a timeout. You can click Learning the startup instruction on the ECC800-Pro
WebUI and start the learning mode again.
On the Controls tab page, choose Exiting the learning mode, and click Submit.
On the Controls tab page, select Air conditioner startup and click Submit. The
re-authentication page is displayed. Enter Login Password and click Submit.
Check whether the smart cooling product is powered on. If yes, the control function is
enabled. If no, rectify the faults and perform the operation again.
After you perform Learning the startup instruction on the WebUI, check the indicator status. If
the indicator on the infrared remote control module blinks yellow, it indicates that the infrared
remote control module enters the infrared learning state. If the green indicator blinks, it indicates
learning success of the key code. If the indicator is steady yellow, it indicates learning failure and
you need to rectify the faults and perform Learning the startup instruction again.
After you perform Air conditioner startup on the WebUI, check whether the smart cooling product
starts. If it starts, the control function works; if it cannot start, rectify the fault and perform the
preceding steps again.
After the device is powered on, the yellow indicator is steady on, indicating that the
device has not learned the infrared encoding. The green indicator blinks, indicating that
the device has learned the infrared encoding. The infrared remote control module is in
normal operating mode by default.
Press the SW button on the infrared remote control module for more than 3s. Then the
indicator blinks yellow and the infrared remote control module enters learning operating
mode.
Press the SW button once quickly and the infrared remote control module enters the
waiting state for learning. Direct the remote control of the smart cooling product to the
infrared receiving place on the infrared remote control module, and press the power
button once. If the green indicator blinks, it indicates learning success of the first key
code.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
172

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents