Setting Ecc800-Pro Cascading - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
changed parameters, and the numbers of parameters that are successfully
changed and failed to be changed are displayed beside Submit.
Step 4 Select the All Configured Data tab page to view the configured device
performance parameters.
----End

6.2 Setting ECC800-Pro Cascading

If multiple smart modules (≤ 3) are installed in the same room and the customer
has not deployed the NetEco, multiple ECC800-Pros can be cascaded for
management. To set the cascading function, follow the procedure in this section.
Prerequisites
Cascaded ECC800-Pros communicate with each other properly.
Context
A maximum of three ECC800-Pros can be cascaded. After the IP addresses of other
smart module ECC800-Pros in the room are added to an ECC800-Pro, their active
alarms and PUE data can be displayed and viewed.
You can click links on the cascading management page of the master ECC800-Pro
to display the login pages of the other ECC800-Pros. Then, you can log in to view
the details.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Smart Module Cascading.
Step 3 Click Add. In the displayed New Smart Module Cascading dialog box, enter the
IP addresses of the ECC800-Pros to be cascaded.
Step 4 Click Confirm.
Step 5 Choose Home > Multi-Module Monitoring. The information about the cascaded
ECC800-Pros is displayed.
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
127

Hide quick links:

Advertisement

Table of Contents
loading