Viewing The Power Supply Links Diagram - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
3.
4.
5.
Step 2 View the power information on the ECC800-Pro app.
1.
2.
3.
----End

6.11.4 Viewing the Power Supply Links Diagram

Procedure
Step 1 Connect the pad to the WiFi network of the ECC800-Pro in the room.
Step 2 Log in to the ECC800-Pro app as an administrator.
Step 3 View the power supply status of the smart module and basic information about each device in
real time to quickly locate faults.
Issue 06 (2020-04-22)
View the power usage information about each cabinet, such as the Current Power (kW),
Power Consumption (kWh), and Load Percentage (%).
Choose Monitoring > System. In the Power Information area on the Running Info tab
page, you can view the power information about the smart module.
Choose Home > Plan View. In the PUE area, you can view the transient mPUE.
Transient mPUE = Total input power/Total IT power of the smart module. For example, if a
PDU8000 with the total input power of 5 kW connects to the smart module, whose total IT power is
3.6 kW, the transient mPUE = 5 kW/3.6 kW = 1.39.
If the power management is not configured, the PUE area in Plan View displays the average PUE.
Instant is displayed for a transient mPUE.
Connect the pad to the WiFi network of the ECC800-Pro in the room.
Choose Home > Power to view the proportion of used power for each cabinet.
Choose Home > Resource > Power to view the real-time power and rated power for the
entire smart module as well as the real-time power for each cabinet, and check whether
the used power exceeds the alarm threshold.