Setting Temperature And Humidity Values - Huawei NetCol5000-A User Manual

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual

3.2.3 Setting Temperature and Humidity Values

Context
To set T/H control type, Temp control mode, cold aisle sensors 1, 2, and 3, and hot aisle
sensors 1, 2, and 3, log in as the Admin or Engineer user. To set other parameters, log in as
the Admin, Engineer, or Operator user.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
displayed.
Figure 3-4 Setting temperature and humidity values
Step 2 Set the parameters by referring to
Table 3-1 Parameter description
Parameter
T/H control
type
Issue 02 (2016-11-30)
You are not recommended to modify the parameters not listed in
Description
Sets Cold-aisle,
Hot-aisle,
Return-air, or
Supply-air as
required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Table
3-1.
Configuration Principle
Return-air: For a hot aisle, select Return-air
to control the temperature and humidity
around the air return vent of the precision air
conditioner.
Supply-air: For a cold aisle, select Supply-air
to control the temperature and humidity
around the air supply vent of the precision air
conditioner.
Cold-aisle: For a cold aisle, select Cold-aisle
to control the temperature and humidity of the
aisle. The temperature and humidity values
come from the humidity and temperature
sensor in the aisle.
Hot-aisle: For a hot aisle, choose Hot-aisle to
control the temperature and humidity of the
aisle. The temperature and humidity values
3 Power-on Commissioning
Figure 3-4
Table
3-1.
is
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-aNetcol5000-cNetcol8000-c

Table of Contents