Chapter 2 General Specifications
2
68

RO662S

Item
No. of input point
Load Voltage
Maximum Load
Minimum Load
Delay time
ON Delay
OFF Delay
Leakage current when OFF
External connections
Common
No. of commons
configuration
No. of input points
per common
Common polarity
Current consumption
Withstand voltage
External Relay Coil Power Required
ON/OFF life of relays
Weight
Circuit Configuration
Terminal Connections
8 points (each point isolated)
110Vdc, +10%(Max.) /240Vac, +10%(Max.)
2A/point (resistive load) and 1A/point (inductive load) at
240Vac/24Vdc
0.5A/point (resistive load) and 0.1A/point (inductive
load) at 110Vdc
50mW (5Vdc or more)
10ms or less
15ms or less
0mA or less
18-point terminal block
1
1 point
No polarity
40mA (5Vdc) or less
1500Vac /1minute
24Vdc ± 10%-100mA/all points ON (10mA/ point)
Electrical : See the figures of life curves of the output
relay, Mechanical : 20milion times
Approx. 250g
LED Display
0
1
2
3
4
No over load protection fuses
N o over load protection fuses
are built into this module.
5
are built into this m odule.
Therefore connect fuses
Therefore connect fuses
6
externally suitable to the
externally suitable to the
current capacity.
7
current capacity.
24v dc
model 2000 Sequence Controller S2 User's Manual -Basic Hardware-
RO662S
0
1
2