Ro663 - Toshiba V Series User Manual

Sequence controllers
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 2 General Specifications
2
66

RO663

Item
No. of input point
Load Voltage
Maximum Load
Minimum Load
Delay time
ON Delay
OFF Delay
Leakage current when OFF
External connections
Common
No. of commons
configuration
No. of input points
per common
Common polarity
Current consumption
Withstand voltage
External Relay Coil Power Required
ON/OFF life of relays
Weight
Circuit Configuration
Terminal Connections
1
3
5
7
8
A
C
E
C O M 1
-
2 4 V d c
16 points
24Vdc, +20%(Max.) /240Vac, +10%(Max.)
2A/point (resistive load), 1A/point (inductive load),
8A/8 points common
50mW (5Vdc or more)
10ms or less
15ms or less
0mA or less
20-point terminal block
2
8 point
No polarity
80mA (5Vdc) or less
1500Vac /1minute
24Vdc ± 10%-90mA/all points ON (5mA/ point)
Electrical : See the figures of life curves of the output
relay, Mechanical : 20milion times
Approx. 300g
0
2
4
6
No over load protection fuses
N o over load protection fuses
C O M 0
are built into this module.
are built into this m odule.
Therefore connect fuses
Therefore connect fuses
9
externally suitable to the
externally suitable to the
B
current capacity.
current capacity.
D
F
+
model 2000 Sequence Controller S2 User's Manual -Basic Hardware-
RO663
0
1
7
COM0
8
F
COM1
+
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

2000