Unit Configuration - Toshiba V Series User Manual

Sequence controllers
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

1.2.3

Unit Configuration

The main base is used as the basic unit.
The controller module for duplex system should always be mounted on S0, the leftmost
slot of the slots provided for station modules. Other required station modules including
the duplexing interface (IF619) can be mounted from the subsequent slots (S1 to S4).
The expansion interface (IF661) is mounted on the expansion interface slot.
Note that the G2 I/O module cannot be mounted on the basic unit in the duplex system.
Be sure to mount the space module (SP600) on the slot which is not used and the I/O
bus module slot on BU648E.
Type
BU648E
BU643D
Type
BU648E
BU643D
Type
BU668
BU666
BU664
*1: The number enclosed in parentheses is the maximum number of I/O modules that
can be mounted when IF658 is mounted in the first layer unit.
6F8C0836
Table 1-7 Main base
Slot No.
Description
for Station Module
For
5
Basic unit
4
3
2
1
For
4
Basic unit
3
2
1
Table 1-8 Modules mounted on the main base ( Ο: Yes, X : No)
Module type
Station
Controller module
module
Network module
Interface for
IF619
duplex system
I/O module
All
Station
Controller module
module
Network module
Interface for
IF619
duplex system
I/O module
All
Table 1-9 Expansion base
Description
Space slot No.
For
1
Expansion
0
unit
0
1.2 S2 Configuration (Station Module:Duplex Configuration)
Slot No.
for Direct I/O Module
0
0
0
0
0
0
0
0
0
S0
S1
S2
S3
S4
O
O
O
O
O
X
O
O
O
O
X
O
O
O
O
X
X
X
X
X
O
O
O
O
X
O
O
O
X
O
O
O
X
X
X
X
Slot No.
for Direct I/O Module
*
S0: Mount IF658 on S1.
1
8(7)
1
Mount IF658 on S0.
*
6(5)
1
*
4(3)
Remarks
(1) Mount the
controller
module on slot
S0.
(2) 2) I/O modules
cannot be
mounted.
S5
S6
S7
S8
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Remarks
13