Fl611/Fl612 - Toshiba V Series User Manual

Sequence controllers
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

FL611/FL612

Transmission medium
Topology
No. of stations
Transmission cable
Transmission cable
length
Transmission speed
Access method
Communication service Cyclic transmission/message transmission
Transmission capacity
Response
RAS information
Display
Current consumption
Weight
External connection
Supplementary
1. FL611 and FL612 are modules connecting to the G2 I/O bus.
2. For details, see "FL-net Common Operation Manual" (6F8C1068).
3. FL-net has two transmission protocol versions. Take care of selecting the equipment
because devices having different versions cannot communicate.
FL611: Supports FA control network [FL-net(OPCN-2)] protocol version 1.00
FL612: Supports FA control network [FL-net(OPCN-2)] protocol version 2.00
6F8C0836
Item
10BASE5
Bus
254 stations/system
AUI cable for Ethernet
2.5km/system
500m/segment
10Mbps
FA link protocol
8192 word + 8192 bits
50ms or less/32 stations in 2048 words + 2048 bits
Node status
In-ring node map
Cyclic node map
Node shutdown information
CPU operation, network participation, transmission and receiving,
access status, 10BASE-T cable connection, collision, parameter error
(LED display)
650mA or less (at 5VDC)/500mA or less (at 12VDC, only when
10BASE5 is connected)
Approx. 500g
10BASE5
D-SUB9 pin (female)
12Vdc
0V
FG
AUI power supply terminal block
2.3 I/O Module Specification
FL611/FL612
10BASE-T
UTP cable for Ethernet
500m/system
100m/segment
10BASE-T
AUI
Modular connector
+12Vdc
10BASE5 and 10BASE-T are automatically
switched.
0V
10BASE-T has priority over 10BASE5 if both
are connected.
FG
(The HUB power should be turn on in advance.)
2
HUB
117