Chapter 1 System Configuration
1.1.3

Unit configuration

1
6
Some examples of minimum and maximum configurations of the single system station
module are shown in this paragraph.
The main base is used as the basic unit. The controller module should always be
mounted on S0, the leftmost slot of the slots provided for station modules. Other required
station modules can be mounted from the subsequent slot (S1 to S4).
I/O modules for digital, analog and open transmission can also be mounted on the slots
for station modules. Note that other network modules, communication modules and high
function modules cannot be mounted on these slots.
The I/O modules should be mounted at the right side of the station modules.
Type
Description
BU648E
For
Basic unit
BU643D
For
Basic unit
Table 1-4 Modules mounted on the main base ( Ο: Yes, X : No)
Type
Module type
BU648E
Station
module
I/O module
BU643D
Station
module
I/O module
*3: Communication, high function analog, high function I/O and exclusive network
modules
Type
Description
BU668
For
Expansion
BU666
unit
BU664
Table 1-3 Main base
Slot No.
Slot No.
for Station Module
for Direct I/O Module
5
4
3
2
1
4
3
2
1
S0
S1
Controller module
O
O
Network module
X
O
Digital/analog/
X
O
open transmission
Other *3
X
X
Controller module
O
O
Network module
X
O
Digital/analog/
X
O
open transmission
Other *3
X
X
Table 1-5 Expansion base
Slot No.
Space slot No.
for Direct I/O Module
1
0
0
model 2000 Sequence Controller S2 User's Manual -Basic Hardware-
Remarks
4
5
6
7
8
0
1
2
3
S2
S3
S4
S5
S6
S7
O
O
O
X
X
X
O
O
O
X
X
X
O
O
O
O
O
O
X
X
X
O
O
O
O
O
O
O
O
O
X
X
Remarks
8
S0: Space slot
6
4
S8
X
X
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

2000