Digital Mode; Connecting Piping For Closed Tank, Condensing Atmosphere Level Measurement; Electronics Housing - ABB Platinum standard Series Product Instruction

Smart level transmitter
Table of Contents

Advertisement

N O TE S :
1. A LL H O R IZ O N TA L L IN E S S H O U LD S LO P E AT LE A S T 8 3 M M /M (1 IN ./FT )
D O W N W A R D TO B LO W D O W N VA LV E S .
2. T R A N S M ITT E R M U S T B E T H O RO U G H LY V E N T E D TO AVO ID
M E A S U R E M E N T E R RO R S .
3. M O U N T T R A N S M ITT E R B E LO W V E S S E L TA P S.
H
A
1-IN . VA LV E S .
B
1/4 -IN . VA LV E S .
C
E Q U A LIZ IN G VA LV E .
D
1/2 -IN . B LO W D OW N VA LV E S .
1/2 -IN . T E E S
E
F
1-IN . N IP P L E S (TO P A N D B O T TO M ).
G
1/2 -IN . P IP E O R 5/8 O .D . T U B IN G (T O B LO W D OW N VA LV E S ).
H
2-IN . S U P P O RT P IP E (C U S T O M E R S U P P LIE D ).
I
P L U G S O R V E N T VA LV E S FO R F IL LIN G A N D V E N T IN G.
WBPEEUI110504A0
C
+
1/2 -IN . T U B IN G
Figure 3-10. Connecting Piping for Closed Tank,
Condensing Atmosphere Level Measurement
The TEST terminals have the same four to 20-milliampere sig-
nal as the PWR/OUTPUT terminals. Loosen the - (negative)
TEST terminal jumper screw ½-turn for calibration or testing.
Signal wiring should be shielded. Use twisted pairs for best
results. Connect the shield at the ground terminal inside the
electronics housing (Fig. 2-4) or at the receiver.
NOTE: Connect the shield at one end only. Connecting the shield at
both ends may result in a ground loop condition.

DIGITAL MODE

In the digital mode of operation there is no four to
20-milliampere signal. The transmitter draws less than four
milliamperes to maintain operation (Fig. 2-5).
NOTE: Refer to the Field Bus I/O Module (IMFBS01) Instruction
for wiring practices and output update times.
G
I
B
E
D
SETUP AND PHYSICAL INSTALLATION
INSTALLATION
A
F
T 02 2 24 A
3 - 15