N O TES :
1 . A L L H O R IZ O N TA L L IN E S S H O U L D S L O P E AT L EA S T 8 3 M M /M (1 IN ./FT ) D O W N W A R D TO B L OW D O W N VA LVE S.
2 . TR A N S M ITTE R M U ST BE TH O RO U G H LY V EN T ED TO AVO ID M EA S U R E M E N T E R R O R S.
3 . M O U N T TR A N S MIT TE R BE L O W V ES S EL TA P S.
≥
4 . h x S G
U R L .
2
F
A
E Q UA L IZIN G VALVE .
B
1 /4 -IN . TO 1 /2 -IN . VA LVE S.
C
1 /2 -IN . BL O W D OW N VA LV E S.
D
1 /2 -IN . PIP E O R 5 /8-IN . O .D. T U BIN G (TO B LO W D O W N VALV E ).
C O N N EC T IO N IN S ID E O R B OTTO M O F TAN K (F ILTE R SC R E E N S
E
R E C O M M E N D ED F O R B OT TO M -O F-TA N K C O N N E C TIO N S ).
F
2 -IN . SU P P O R T PIP E (C U S TO M E R S U P PL IE D ).
Wiring
WBPEEUI110504A0
A
–
+
Figure 3-8. Connecting Piping for Closed Tank, Noncondensing
Atmosphere Level Measurement
There
are
Type PTSD pressure transmitter.
NOTE: Never connect the loop wiring to the test terminals.
ANALOG MODE
In the analog mode of operation, the electrical connections are
made in the typical two-wire, four to 20-milliampere configura-
tion as shown in Figure 2-4. Both a + (positive) and -
(negative)
the signal leads.
NOTE: Insure that the temperature rating of the wire is suitable for
the environment.
The signal terminals located in the electronics housing accept
wire sizes up to 14 AWG. The signal wiring supplies all power
to the transmitter. The power supply limits are 12 to 53 VDC
(12 to 42 VDC for certified application) across the transmitter
inputs. Refer to Figure
the equation:
1 /2 -IN . VA LVE S
B
two
possible
wiring
terminal are provided at the transmitter to identify
2-4
for the load resistance limits, or use
SETUP AND PHYSICAL INSTALLATION
INSTALLATION
E
D
C
T 02 2 22 A
configurations
for
the
3 - 13