ABB PGX100 Operating	 Instruction

ABB PGX100 Operating Instruction

Gauge and absolute pressure transmitters
Table of Contents

Advertisement

Quick Links

A B B M E A S U R E M E N T & A N A LY T I C S | O P E R AT I N G I N S T R U C T I O N
PGX100 and PAX100
Gauge and absolute pressure transmitters
Introduction
PGX100/PAX100 model
The present manual provides information on
installing, operating, troubleshooting the PGX100
and PAX100 pressure transmitter models. Every
section of the present manual is specifically
dedicated to the specific phase of the transmitter
lifecycle starting from the receipt of the transmitter
and its identification, passing to the installation, to
the electrical connections, to the configuration and
to the troubleshooting and maintenance operations,
as applicable.
The pressure transmitters model PGX100 and
PAX100 are field mounted, microprocessor based
electronic transmitters. Accurate and reliable
measurement of gauge and absolute pressure is
provided, in the even most difficult and hazardous
industrial environments. These models can be
configured to provide specific industrial output
signals according to 4 to 20mA with HART digital
communication.
Engineered solutions for all
applications
Measurement made easy
For more information
Further publications for PGX100 and PAX100 family
of pressure products are available for free download
from:
www.abb.com/pressure
or by scanning this code:
Download the PGX100 and PAX100 control drawing
by scanning this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB PGX100

  • Page 1 Introduction For more information — PGX100/PAX100 model The present manual provides information on Further publications for PGX100 and PAX100 family installing, operating, troubleshooting the PGX100 of pressure products are available for free download and PAX100 pressure transmitter models. Every from: section of the present manual is specifically www.abb.com/pressure...
  • Page 2: Table Of Contents

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Contents Safety .
  • Page 3 P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Operation (only HART version) .
  • Page 4: Safety

    ABB-authorized centers are excluded from this. intended to amend these. All obligations of ABB arise from the conditions of the relevant Technical limit values sales agreement, which also contains the solely binding warranty regulations in full.
  • Page 5: Operator Liability

    The owner must observe the proper regulations for shipping purposes. All devices sent back to ABB must be free from any hazardous materials (acids, alkalis, solvents, etc.).
  • Page 6: Safety Information For Inspection And Maintenance

    ABB and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 7: Transmitter Overview

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C 2 Transmitter overview Transmitter components overview Bracket...
  • Page 8: Range And Span Consideration

    (SR) process active in ABB. Range and span consideration The PGX100 and PAX100 Transmitter data sheet provides all information concerning the Range and Span limits in relation to the model and the sensor code. The terminology currently used to define the various parameters is as follows: •...
  • Page 9: Opening The Box

    The instrument may be used as a pressure accessory (category III) as defined by the Pressure Equipment Directive 2014/68/EU. In this case you will find the number of the notified body (0474) that have verified the compliance. PGX100 and PAX100 pressure transmitters are in compliance with EMC 2014/30/EU.
  • Page 10: Handling And Storage

    IP protection and designation The instrument does not require any special precautions during The housings for PGX100 and PAX100 transmitters are certified handling although normal good practice should be observed. as conforming to protection type IP67 / IP68 / IP69K (according to ISO 20653) or NEMA 4X (according to NEMA 250).
  • Page 11: Mounting The Transmitter

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Mounting the transmitter Transmitter factory configuration consideration The PGX100 and PAX100 pressure transmitter in your hands has been factory calibrated to reflect the published declared performance specification; no further calibration is required in normal condition.
  • Page 12: Sealing And Screw Connections

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 13: Measuring Pipe

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Measuring pipe In order for the pipes to be laid correctly, the following points must be observed: •...
  • Page 14: Transmitter Wiring

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C 5 Transmitter wiring WARNING General Risks .
  • Page 15: Wiring Procedure

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 16: Output (Hart) Transmitter Wiring

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 17: Commissioning

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C 6 Commissioning General remarks Output current limits for HART and analog version...
  • Page 18: Local Display

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 19: Adjusting Lower Range Value / Oblique Sensors

    Variant B, with touchscreen controls on the optional LCD display. There are two options (variant A or B) for calibrating the For PGX100/PAX100 models, when in operating mode, the 4 to 20 mA output signal directly on the transmitter. device shows respectively “Z-S” on the left and configuration menu icon on the right side of the display.
  • Page 20: Installing/Removing The Lcd Display

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Installing/Removing the LCD display IMPORTANT Carefully insert the flat connector following the required...
  • Page 21: Pressure Sensor Ventilation (Pgs100 Only)

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Pressure sensor ventilation (PGX100 only)
  • Page 22: Operation (Only Hart Version)

    LCD menu structure PGX100/PAX100 models feature only the Easy Setup menu in a dedicated structure, different from other HART versions. Once accessed the menu should be completed until the last step is reached, then to return to the normal display view.
  • Page 23: Easy Setup Menu

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Easy setup menu Set PV To Zero Set the input measured value to 4 mA...
  • Page 24: Error Messages

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C 8 Error messages LCD display messages The LCD HMI in case of transmitter errors or malfunctioning is capable of displaying specific error/fault messages to help the user...
  • Page 25 P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 26 P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C HMI - Code Error...
  • Page 27: Qr Code Digital Advanced Diagnostic (Dad)

    The Channel Partner Support QR Code is part of the personalization option set available at ABB channel partners. Using the above, customer can always have on hand and directly in the field an immediate contact point for assistance and support.
  • Page 28: Maintenance / Repair

    PGX100 and PAX100 user repair is not permitted. • the wear (corrosion) When replacing or repairing individual components, original PGX100 transmitters have a reference port vented to the spare parts must be used. atmosphere and duly protected (see picture). During...
  • Page 29: 10 Hazardous Area Considerations

    IECEx scheme. The cable gland must conform to IP rating IP 67. • When the PGX100/PAX100 pressure transmitter is used for The smoldering temperature of the dust must be at least 75 K group III Db, do not install in area that is subject to flowing dust.
  • Page 30: Hazardous Atmospheres

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C Hazardous atmospheres ATEX transmitter with the following types of protection: IECEx transmitter with the following types of protection:...
  • Page 31: Canadian Standards Association (Us)

    P G X 1 0 0 A N D PA X 1 0 0 | P R E S S U R E T R A N S M I T T E R S | O I/ P G X / PA X 1 0 0 - E N R E V. C .
  • Page 32 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

This manual is also suitable for:

Pax100

Table of Contents