INTRODUCTION

OPERATOR INTERFACE

CONFIGURATION PROCEDURE

ID Tag

Select Mode

WBPEEUI110504A0

SECTION 5 - OPERATING PROCEDURES

This section addresses start-up procedures, configuration, and
monitoring of the Type PTSD Platinum Standard Smart Pres-
sure Transmitter and the procedures that make it operational.
The Type PTSD pressure transmitter can be monitored and
controlled using the Type STT terminal. Connect the Type STT
terminal across the signal wires in a parallel connection
(Figs.
2-4
and 2-5) wherever there is convenient access. (For
point-to-point wiring, the Type STT terminal must be con-
nected between the transmitter and the 250-ohm resistor.)
Refer to the Type STT Smart Transmitter Terminal
Instruction
for
detailed
procedures.
Configuration of the transmitter includes defining an identifi-
cation tag, primary lower and upper range values, digital or
analog mode of operation, primary engineering units, second-
ary engineering units and secondary lower and upper range
values, output parameters, cell temperature alarm limits, and
a damping constant. Use the CONFIGURE key and follow the
step-by-step procedures in the Type STT Smart Transmitter
Terminal Instruction. Once a configuration has been saved
in the Type STT terminal, download it to a connected transmit-
ter using the SEND CONFIG key. The remainder of this section
explains the configuration parameters.
The transmitter ID tag is a 14-character alphanumeric tag that
can be programmed into the transmitter. It is different than
the transmitter address. The ID tag is entered during configu-
ration for identification purposes. To display the ID tag on the
terminal screen, press the STATUS key.
Select either the analog mode or the digital mode. If the digital
mode is selected, the transmitter does not output a four to
20-milliampere signal in proportion to the input. The output
will be locked below four milliamperes. If the analog mode is
specified instead, the transmitter will provide a four to
20-milliampere output signal.