TROUBLESHOOTING
Table 6-2. Output Troubleshooting
Fault
Low output or no output
(continued)
ERROR MESSAGES AND CORRECTIVE ACTION
6 - 6
Probable Cause
Pressure piping.
Device in digital mode.
Transmitter electronics
connections.
Transmitter electronics failure.
Cell.
(continued)
Corrective Action
Check that pressure connection is
correct.
Check for leaks or blockage.
Check that blocking valves are
fully open and bypass valves are
tightly closed.
Check for entrapped gas in liquid
lines and for liquid in dry lines.
Check that density of fluid in pres-
sure piping is unchanged.
Check for sediment at transmitter
process connection.
If analog output is desired, config-
ure the transmitter using CONFIG-
URE key, then press SEND
CONFIG.
Check for shorts in cell leads.
Make sure pins and receptacles
are clean.
Check cell connections.
Press STATUS key and refer to
Table
6-1
and Figure 6-1.
Press STATUS key and refer to
Table
6-1
and Figure 6-1.
WBPEEUI110504A0