Connection Mode "Digital Input; Table 34: Overview Of Adjustable Parameters For The Digital Inputs - WAGO MOVILINK SPEEDWAY 767 Manual

Rs-232, rs-485, 2 interfaces 2 x m12 + 4 digital inputs/outputs 2 x m12, two inputs/outputs per connector
Table of Contents

Advertisement

62
Parameterizing
7.3.2

Connection Mode "Digital Input"

Table 34: Overview of adjustable parameters for the digital inputs

Parameter
Connection mode
Designation
Input value
Signal Inversion
Filter time
Substitute value strategy
Substitute value
Simulation input value
* Default
** The last value is the value output to the contact before occurrence of the respective interruption.
This can be, for example, an input value or a "simulation value".
Pos : 31.15 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
767-5204 MOVILINK® Interface (RS-232, RS-485)
Description
Mode display
Electronic marking field (max. 40 characters)
The input state is indicated in this field. When simulation is
activated, the field becomes a checkbox.
Activate the checkbox to simulate the state "1" in the process image
independent of the input.
You can invert the currently pending input signal here.
Checkbox deactivated*:
Input signal is mapped in the process image as attached to the input
Checkbox activated:
Input signal is mapped inverted in the process image
Set the input filter for the measured signals here. You have the
following options:
- None
- 0.1 ms
- 0.5 ms
- 3 ms*
- 15 ms
- 20 ms
This is used, for example, to transfer the substitute value or the last
input value in the event of a low voltage U
following options:
- Switch to substitute value*
- Keep last value**
Here you can enter the process value that is transmitted in the case
of an error. In case of error (e.g. low voltage U
with the "Switch to substitute value" substitute value strategy.
Checkbox deactivated:
0*
Checkbox activated:
1
Activate this checkbox to switch input simulation on. The field for
the input value then becomes a checkbox for the simulation value.
WAGO-SPEEDWAY 767
. You have the
A
), the value is used
A
Manual
Version 1.1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-5204

Table of Contents