4 Commissioning

4.1 General information

This section describes a standard application commissioning procedure.
The preliminary operations for commissioning ADV200 drives are described in chapter 7 of the "ADV200
Quick Start Guide - Specifications and connection".

4.2 Requirements

The Electrical Line Shaft application for ADV200 drives requires at least firmware version 5.00 of the drive
with the relative optional cards for encoder signal acquisition.
The ADV200 firmware version supports asynchronous (ASY) and synchronous (SYN) motors.
To install the application you must have a PC, version 1.6.27 or higher of the Gefran GF Express software
with Catalog, the drive RS485 - PCI COM connection kit and the set-up CD.
The Electrical Line Shaft application set-up CD contains an automatic procedure that copies the required
files in the specific folders of the GF Express catalog. Once this is complete, the set-up procedure normally
requires the following files with the paths as shown:
The files in the Electrical Line Shaft application
adv_els_5_00_asy_v1_0__A1.fl2
adv_els_5_00_asy_v1_0__A2.fl2
adv_els_5_00_syn_v1_0__A1.fl2
adv_els_5_00_syn_v1_0__A2.fl2
are copied to
...\Programmi\Gefran\Catalog\Drives\Inverter\ADV200\ADV200_5_X_0\Service\
Applications\
Drive and Electrical Line Shaft application parameter structure files
adv_els_5_00_asy_v1_0.gft
adv_els_5_00_syn_v1_0.gft
to
...\Programmi\Gefran\Catalog\ Drives\Inverter\ADV200\ADV200_5_X_0

4.3 Initial operations

Check the connections, paying particular attention to shielding (see standard wiring diagrams) in
order to reduce interference to a minimum, especially on encoders.
Set the IPA 558 Application Select parameter to the application where you wish to load the
Electrical Line Shaft (Application 1 or Application 2).
If the Electrical Line Shaft application firmware is not already installed, download it using the GF-
Express "Download firmware" utility. You can either download the application only, or the entire drive
firmware including the application; the latter option is useful if the version of the unit firmware is not
compatible.
Files called "nomefile___A1.fl2" enable the firmware to be downloaded to Application 1, files named
"nomefile___A2.fl2" enable the firmware to be downloaded to Application 2.
NB!
ADV200 drive is supplied with the PID application installed in Application 1; to avoid overwriting this application, we
recommend downloading the firmware to Application 2.
Send a "Drive reset" command.
Open the drive parameters file containing the Electrical Line Shaft parameters (.gfe)
User Guide Electrical Line Shaft for ADV200
(asynchronous motors – application 1)
(asynchronous motors – application 2)
(synchronous motors – application 1)
(synchronous motors – application 2)