3.6

Connecting the wastewater pump(s)

1 Before connecting the pump, check whether the control unit's motor
protection switch is suitable for the current consumption of the
pump(s) (see nameplate).
▶ Adjust the motor protection switch to the pump's nominal current
(see pump's nameplate)
▶ Pull the connection cable through the housing opening(s) and
connect to the mains cable in the same way as the screw connection.
▶ Establish connections in accordance with the connection diagram.
Installation
34 / 148