2.1.2.6 Technical Data
Module Specific Data
Number of inputs
Voltage supply
Current consumption
Sensor types
(the free configurable variation supports all
listed sensor types)
Sensor connection
Temperature range
Resolution
Conversion time
Response delay
(time from starting or connecting the sensor to
the first proper measured value)
Measuring error
Temperature coefficient
Isolation
Measured current
Bit width
Dimensions (mm) W x H x L
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
EMC-Emission of interference (CE)
EMC-Immunity to interference
(Ship building)
EMC-Emission of interference
(Ship building)
WAGO-I/O-SYSTEM 750
I/O Modules
(internal)
max.
max.
25°C
typ.
750-461, (/xxx-xxx) [2 AI Pt100/ RTD]
2
via system voltage DC /DC
80 mA
Pt 100 (factory preset),
optionally orderable variants for
Pt 1000,
Ni 100, Ni 120, Ni 1000 TK6180,
Ni 1000 TK5000, resistance measuring.
3-wire (factory preset) or 2-wire
-200 °C ... +850 °C (Pt)
-60 °C ... +250 °C (Ni100, Ni100TK6180)
-30 °C ... +122 °C (Ni100TK5000)
0,1 °C
320 ms (per channel)
960 ms (per channel for 750-461/000-006)
4 s
12 s (for 750-461/000-006)
< 0.2 % of full scale value
< 0.01 % /K of full scale value
< 0,001 % /K of full scale value (for
750-461/000-006)
500 V (System/Supply)
0.5 mA
2 x 16 bits data
2 x 8 bits control/status (option)
12 x 64* x 100
* from upper edge of 35 DIN rail
ca. 55 g
acc. to EN 61000-6-2: 2005
acc. to EN 61000-6-4: 2007
acc. to Germanischer Lloyd (2003)
acc. to Germanischer Lloyd (2003)
• 17