2.1.2.7.1.1 Pt 100
The analog input modules 750-461 and 750-461/000-006 transmit 16-bit
measured values per channel as well as 8 optional status bits to the
coupler/controller.
However, accessing the status byte depends on the fieldbus system being used.
Broken wire against R
1)
The measured value can exceed the range from decimal –2000 to 8500 until the limitation
applies.
2.1.2.7.1.2 Pt 1000
The analog input modules 750-461/000-003 transmit 16-bit measured values
per channel as well as 8 optional status bits to the coupler/controller.
However, accessing the status byte depends on the fieldbus system being used.
Broken wire against R
1)
The measured value can exceed the range from decimal –2000 to 8500 until the limitation
applies.
WAGO-I/O-SYSTEM 750
I/O Modules
Resis-
Tem-
perature
tance
°C
<-200.0
10.00
-200.0
18.49
-100.0
60.25
0.0
100.00
100.0
138.50
200.0
175.84
500.0
280.90
750.0
360.47
800.0
375.51
850.0
390.26
>850.0
>390.26
L
Temperature values below 0 °C are represented in two's complement binary form.
Tem-
Resis-
perature
tance
°C
<-200.0
100.00
-200.0
184.93
-100.0
602.54
0.0
1000.00
100.0
1385.00
200.0
1758.40
500.0
2808.96
750.0
3604.65
800.0
3755.09
850.0
3902.62
>850.0
>3902.62
L
Temperature values below 0 °C are represented in two's complement binary form.
750-461, (/xxx-xxx) [2 AI Pt100/ RTD]
750-461, /000-006 (Pt 100)
Numerical value
binary
'1000.0000.0000.0001' 0x8001
'1111.1000.0011.0000' 0xF830
'1111.1100.0001.1000' 0xFC18
'0000.0000.0000.0000' 0x0000
'0000.0011.1110.1000' 0x03E8
'0000.0111.1101.0000' 0x07D0
'0001.0011.1000.1000' 0x1388
'0001.1101.0100.1100' 0x1D4C
'0001.1111.0100.0000' 0x1F40
'0010.0001.0011.0100' 0x2134
'0010.0001.0011.0100' 0x2134
'0010.0001.0011.0100' 0x2134
750-461/000-003 (Pt 1000)
Numerical value
binary
'1000.0000.0000.0001' 0x8001
'1111.1000.0011.0000' 0xF830
'1111.1100.0001.1000' 0xFC18
'0000.0000.0000.0000' 0x0000
'0000.0011.1110.1000' 0x03E8
'0000.0111.1101.0000' 0x07D0
'0001.0011.1000.1000' 0x1388
'0001.1101.0100.1100' 0x1D4C
'0001.1111.0100.0000' 0x1F40
'0010.0001.0011.0100' 0x2134
'0010.0001.0011.0100' 0x2134
'0010.0001.0011.0100' 0x2134
Process Image
Status-
1)
byte
hex.
dec.
Hex.
-32767
0x41
-2000
0x00
-1000
0x00
0
0x00
1000
0x00
2000
0x00
5000
0x00
7500
0x00
8000
0x00
8500
0x00
8500
0x42
8500
0x42
Status-
1)
byte
hex.
dec.
Hex.
-32767
0x41
-2000
0x00
-1000
0x00
0
0x00
1000
0x00
2000
0x00
5000
0x00
7500
0x00
8000
0x00
8500
0x00
8500
0x42
8500
0x42
• 21
LED
Error
AI 1, 2
on
off
off
off
off
off
off
off
off
off
on
on
LED
Error
AI 1, 2
on
off
off
off
off
off
off
off
off
off
on
on