Press the moisture resistant packing into place
Create a mounting hole
• To enhance the PL's maintainability, operability and ventilation, allow at least 50 mm
or more clearance between the PL and any other objects. (The clearance must be
large enough to allow you to insert or remove expansion boards and to attach connec-
tors.)
50mm
4-2
Moisture resistant
packing
Rear
panel
Panel
Mounting hole
> <
1.6 - 10.0 mm
> <
Side panel
^
50mm
^
^
50mm
^
Installation and Wiring
Place the PL on a level surface with the dis-
play panel facing downward. Fit the PL's
moisture resistant packing into the resin
bezel's groove.
Create a hole for mounting the PL, like that
pictured here. These two items, the moisture
resistant packing and the mounting brackets are
required when installing the PL.
See "2-5 External Appearance and
Dimensions"
• To obtain the maximum level of mois-
ture resistance, mount the PL on a
smooth, flat surface.
• The panel itself can be from 1.6 to 10
mm thick.
Rear panel
^
50mm
^
50mm
^
50mm
^
50mm