gefran AFE200 Series Instruction Manual page 81

Active front end regenerative power supply unit
Table of Contents

Advertisement

0
Inactive
1
EmgStop&Alarm
If the command is set to Inactive, pressing the Stop key on the keypad is ineffective.
If the command is set to EmgStop&Alarm, pressing the Stop key disables the drive
and the Emg stop alarm is generated.
The drive is automatically disabled and waits for the Alarm reset command (RST key,
see chapter 6.6.1).
Menu
PAR
Description
6.4
1010
Commands safe start
This parameter is used to define whether the safe start command is disabled or ena-
bled at drive power-on
0
Off
1
On
If set to Off the safe start function is disabled. Therefore, if the drive is powered with
the hardware signal present on terminal 7 the drive could start.
If set to On the safe start function is enabled. Therefore, if the drive is powered
with the hardware enabling signal on terminal 7 it will not start. Open the hardware
enabling contact on terminal 7 and then close it again to enable the drive to accept
subsequent commands.
Menu
PAR
Description
6.5
1012
Dig local/remote
Setting Local or Remote operating mode.
0
Local
1
Remote
Writing this parameter is only effective if it is associated with Local/Remote src and if
performed without the hardware enabled on the terminal 7. Press LOC to modify the
value of this parameter 0 < > 1.
To disable the LOC key, set Local/Remote src to a value other than Dig local/re-
mote.
In Remote mode use the Commands remote sel parameter, PAR 1000 to configure
the source of the enable and run commands, which can be Terminal board (Standard
digital input, Expansion card digital input), or Digital (Modbus, Fieldbus).
In Local mode use the Commands local sel parameter, PAR 1002 to configure the
source of the enable commands, which can be Terminal board (Standard digital input,
Expansion card digital input), or Keypad (Start key, Stop key).
Menu
PAR
Description
6.6
1014
Local/remote src
Selection of the origin (source) of the signal that switches between Remote and Lo-
cal.
The signal to be associated with this function can be selected from the "L_DIGSEL3"
selection list.
UM
Type
FB BIT
BIT
UM
Type
FB BIT
ENUM
16
UM
Type
FB BIT
LINK
16
L�DIGSEL3
AFE200 • Instruction Manual
Def
Min
1
0
Def
Min
Remote
0
Def
Min
1012
0
Max
Acc
1
ERW
Max
Acc
1
ERW
Max
Acc
16384 ERW
81