10.6 Electrical data

Input voltage (AFE200-...-4/4A) ����������380 - 15% ... 500 +5% V
Input voltage (AFE200-... -6/6A) ���������500 - 10% ... 690 +10% V
Input frequency ����������������������50/60 Hz ±2%
Maximum line voltage unbalance ���������3 %
THd Input current ��������������������≤ 5%
Cosphi ����������������������������≥ 0.99
Connection to TT and TN Networks �������AFE200-...-4/4A and AFE200-... -6/6A: = Suitable
Connection to IT Networks: �������������AFE200-...-4/4A = Not suitable
AC
Sizes
Heavy duty
AFE200-...-4
@ 400 V
(A)
3220
40
4450
80
5900
160
61320
230
71600
280
72000
340
72500
400
73150
500
73550
560
400kW
600
500kW
760
630kW
950
710kW
1060
900kW
1400
1MW
1500
(1) K
: Derating factor for mains voltage at 460V
v
(2) K
: Derating factor for 50°C ambient temperature (1 % each °C above 40°C)
t
(3) K
: Derating factor for higher switching frequency
f
(4) K
: Derating factor for installation at altitudes above 1000 meters a.s.l.. Value to be applied at each 100 m increase above 1000 m
alt
(up to a maximum of 2000 m).
I.e.: Altitude 2000 m, Kalt = 1,2 *10 = 12% di derating; In derated = 100 - ((12*100)/100) = 88 % In
AC
Sizes
Heavy duty
AFE200-...-6
(A)
71600
150
72000
190
72500
240
73150
300
73550
340 (5)
400kW
360
500kW
455
630kW
570
710kW
645 (5)
900kW
850
1MW
920 (5)
input current
DC
Light duty
Heavy duty
@ 400 V
@ 650 V
ac
ac
(A)
(A)
60
43
85
100
200
171
245
280
340
298
363
400
500
426
532
560
600
597
640
760
950
811
1012
1060
1150
1129
1492
1500
1730
1598
ac
input current
DC
Light duty
Heavy duty
(A)
(A)
190
165
210
240
300
265
330
340
380
375
455
396
570
500
645
627
720
711
920
935
1050
1012
AFE200 • Instruction Manual
AFE200-... -6/6A: = Suitable for sizes (with integrated
EMI filter).
output current
Switching frequency
Default
Light duty
@ 650 V
dc
dc
(kHz)
(A)
64
8
107
8
213
4
298
4
363
4
426
2
532
2
597
2
640
2
811
2
1012
2
1129
2
1226
2
1598
2
1846
2
output current
Switching frequency
Default
Light duty
(kHz)
(A)
210
4
265
2
330
2
375
2
420
2
500
2
627
2
711
2
792
2
1012
2
1265
2
ac
ac
f
sw
Derating factor
Higher
K
K
v
t
(kHz)
(1)
(2)
-
0.9
0.9
-
0.9
0.9
6.8
0.9
0.9
6.8
0.9
0.9
-
0.9
0.9
4
0.9
0.9
4
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
-
0.9
0.9
f
sw
Derating factor
K
Higher
t
K
H
v
eavy
duty
(kHz)
(6)
(7)
-
1
0.9
-
1
0.9
-
1
0.9
-
1
0.9
-
1
0.85
-
1
0.9
-
1
0.9
-
1
0.9
-
1
0.85
-
1
0.9
-
1
0.85
K
f
(@ 8
K
alt
kHz)
(3)
(4)
-
1.2
-
1.2
0.7
1.2
0.7
1.2
-
1.2
-
1.2
-
1.2
-
1.2
-
1,2
-
1,2
-
1,2
-
1,2
-
1,2
-
1,2
-
1,2
K
t
K
Light
alt
duty
(7)
(8)
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2
0.8
1.2