gefran AFE200 Series Instruction Manual page 128

Active front end regenerative power supply unit
Table of Contents

Advertisement

20
External fault
21
Emg stop alarm
22
Power down
23
Prc fbk loss
24
Not Used1
25
Not Used2
26
Not Used3
27
Not Used4
28
Not Used5
29
Not Used6
30
Not Used7
31
Not Used8
32
Not Used9
33
Plc1 fault
34
Plc2 fault
35
Plc3 fault
36
Plc4 fault
37
Plc5 fault
38
Plc6 fault
39
Plc7 fault
40
Plc8 fault
Menu
PAR
Description
15.37
4720
Alm autoreset time
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the AFE product is set to restart.
If some alarms are still enabled the AFE product is set to execute a new attempt at
automatic reset.
At each attempted reset a counter increases. If the limit set in the PAR 4722 Alm
autoreset number parameter is reached the AFE product is set to make no more at-
tempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no
alarms are enabled.
If the parameter is 0 the function is disabled.
Menu
PAR
Description
15.38
4722
Alm autoreset number
Setting of the maximum number of attempted automatic resets.
128
UM
Type
FB BIT
s
FLOAT
UM
Type
FB BIT
UINT16
AFE200 • Instruction Manual
Def
Min
0.0
0.0
Def
Min
20
0
Max
Acc
60.0
ERW
Max
Acc
100
ERW