Note!
For further information regarding electro-magnetic compatibility standards, according to Directive
89/336/EEC, conformity checks carried out on Gefran appliances, connection of filters and mains
inductors, shielding of cables, ground connections, etc., consult the "Electro-magnetic compatibility
guide" on the CD attached to this drive.
26
circuitry.
Ensure that the contactors in the cubicle are suppressed, either with R-C
suppressors for AC contactors or 'flywheel' diodes for DC contactors fitted to
the coils. Varistor suppressors are also effective. This is important when the
contactors are controlled from the AFE200 relay.
Use screened or armored cables for the U-V-W connections and ground the
screen at both ends using the cable clamps
Use the recommended EMI filters, which are listed in section 11.3 of this
manual (conformity with EN61800-3, class C3 with 50 metres of motor cable
with a single inverter supplied by the AFE200).
Use shielded cables in motors to ensure the correct operation of the EMI filter.
AFE200 • Instruction Manual