gefran AFE200 Series Instruction Manual page 112

Active front end regenerative power supply unit
Table of Contents

Advertisement

concerns the use of the standard RS485 serial line.
Example: if the delay in Tx/Rx switching on the master is a maximum of 20ms, the Ser
answer delay parameter must be set to at least 20ms: 22ms
Menu
PAR
Description
14.1.6
3808
Serial swap data
This parameter enables the exchange of the reading of the High and Low parts of the
words for FLOAT type parameters when using the Modbus protocol.
14.2 - COMMUNICATION/FIELDBUS CONFIG
Menu
PAR
Description
14.2.1
4000
Fieldbus type
Setting of the type of fieldbus to be used..
0
Off
1
CanOpen
2
DeviceNet
3
Profibus
40
Cansync master
41
Cansync slave
If set to 0 no fieldbus is selected.
If set to 1 the CanOpen fieldbus profile is selected.
If set to 2 the ProfiBus-DP fieldbus profile is selected.
If set to 3 the DeviceNet fieldbus profile is selected.
If set to 40 the drive is selected as the master device (*).
If set to 41 the drive is selected as the slave device (*).
(*) Only one drive can be the master device, all the others must be slave devices. When the slave
device is synchronised the SPD0 LED on the keypad lights up; the LED on the master drive is
always off.
Menu
PAR
Description
14.2.2
4004
Fieldbus baudrate
Setting of the communication network speed (Baud Rate).
0
Auto
1
125k
2
250k
3
500k
4
1M
5
9600
6
19200
7
93750
8
187,5k
9
1,5M
10 3M
11 6M
12 12M
Menu
PAR
Description
14.2.3
4006
Fieldbus address
Setting of the node address of the drive when connected to the network.
112
UM
Type
FB BIT
BIT
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
INT16
AFE200 • Instruction Manual
Def
Min
0
0
Def
Min
Off
0
Def
Min
500k
0
Def
Min
3
0
Max
Acc
1
ERW
Max
Acc
5
RW
Max
Acc
12
RW
Max
Acc
255
RW