gefran AFE200 Series Instruction Manual page 118

Active front end regenerative power supply unit
Table of Contents

Advertisement

If set to 2 the datum is assigned a 32-bit count.
If set to 3 16 bits on the channel are reserved for the datum, not used.
If set to 4 32 bits on the channel are reserved for the datum, not used.
If set to 5 the datum is assigned a 16-bit count used by MDPLC.
If set to 6 the datum is assigned a 32-bit count used by MDPLC.
If set to 7 the datum is assigned engineering units on a 16-bit integer.
If set to 8 the datum is assigned engineering units on a 32-bit integer.
If set to 9, the datum is assigned a 16-bit integer engineering unit format not in real
time (5-10ms)
If set to 10 the datum is assigned a 32-bit integer engineering unit format or float for-
mat if the associated parameter is a float-type parameter not in real time (5-10ms)
Note!
If the sys parameter is not assigned, none of the subsequent channels are transferred to the fieldbus,
even if programmed.
Menu
PAR
Description
14.4.3
4184
Dig Fieldbus S->M1
14.4.7
4194
Dig Fieldbus S->M2
14.4.11 4204
Dig Fieldbus S->M3
14.4.15 4214
Dig Fieldbus S->M4
14.4.19 4224
Dig Fieldbus S->M5
14.4.23 4234
Dig Fieldbus S->M6
14.4.27 4244
Dig Fieldbus S->M7
14.4.31 4254
Dig Fieldbus S->M8
14.4.35 4264
Dig Fieldbus S->M9
14.4.39 4274
Dig Fieldbus S->M10
14.4.43 4284
Dig Fieldbus S->M11
14.4.47 4294
Dig Fieldbus S->M12
14.4.51 4304
Dig Fieldbus S->M13
14.4.55 4314
Dig Fieldbus S->M14
14.4.59 4324
Dig Fieldbus S->M15
14.4.63 4334
Dig Fieldbus S->M16
If associated with the relative src, the value of this parameter is sent to the bus.
The user may modify the M->S and by S->M sys parameters. The consistency of the
sys with the parameter assigned to the channel is checked.
Check for channels S->M:
Sys parameter
Count 32
Count 16
Menu
PAR
Description
14.4.4
4186
Fieldbus S->M1 mul
118
UM
Type
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
INT32
FB type
result
32 bit
Sends all 32 bits of input to fieldbus. OK
16_H
Sends all 32 bits of input to fieldbus. OK
16_L
Sends all 32 bits of input to fieldbus. OK
32 bit
Doesn't know whether to send 16H or 16L. Error
16_H
Sends all 16H bits of input to fieldbus. OK
16_L
Sends all 16L bits of input to fieldbus. OK
UM
Type
FLOAT
AFE200 • Instruction Manual
FB BIT
Def
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
32
0
FB BIT
Def
1.0
Min
Max
Acc
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
0
0
ERW
Min
Max
Acc
1.0
1000.0 ERW