12 - ACTIVE CURR CONFIG
Menu
PAR
Description
12.1
2350
Active curr lim Pos
Setting of the drive active current limit for the positive current direction.
Menu
PAR
Description
12.2
2352
Active curr lim Neg
Setting of the drive active current limit for the negative current direction.
Menu
PAR
Description
12.3
2354
Active curr lim sel
Setting of the type of behaviour of the drive in the current limit condition.
0
Off
1
Act clim +/-
2
Act clim src
If set to 0 no specific type of current limitation is set.
If set to 1 the active positive current limit is Active curr lim Pos (PAR 2350) and the
active negative current limit is Active curr lim Neg (PAR 2352).
If set to 2 the active current limits are symmetrical. The value of parameter PAR 2358
is used as the active current reference value (default = Zero)