A 2.2 MS-SL interface cable wiring sizes 400...710kW
Fit the AFE200 MASTER and SLAVE power supplier units inside the electrical
panel. Connect all the power section cables and connect the signal cable for inter-
facing between the 2 drives.
The cable (code 8S860B) for connecting 2 drives is one meter long and has two
quick coupling male MDR connectors at the ends.
AFE200-...-MS
J4 connector
Wiring instructions:
1.
2.
3.
4.
5.
172
AFE200-...-SL
Connect one of the 2 ends of the interface cable to the XSL connector of the
INT-P-ADV-SLAVE card.
Secure the cable using the specific clamp.
Connect the other end of the cable to connector J4 of the INT-SLAVE card
mounted on the INT-P-ADV-MASTER card of the MASTER drive.
Secure the cable in the relative clamp
To prevent the interface cable from coming into contact with the power termi-
nals, fold the excess length of cable inside the SLAVE drive as shown in the
figure and secure it using the specific cable clamps.
AFE200 • Instruction Manual
1.
2.
3.
4.
XSL connector
5.