gefran AFE200 Series Instruction Manual page 126

Active front end regenerative power supply unit
Table of Contents

Advertisement

Enabling of automatic restart after the desaturation alarm Desaturation [5]. This
alarm indicates a short circuit between the phases of the power bridge.
0
Disable
1
Enable
Menu
PAR
Description
15.22
4612
Desat restart time
Setting of the time within which the Desaturation [5] alarm must be reset in order to
perform automatic restart. (Time with alarm signal active + 1000 msec).
Menu
PAR
Description
15.23
4620
IOverC restart
Enabling of automatic restart after the AFE product Overcurrent [4] alarm. This alarm
indicates an overcurrent (or short circuit between phases or towards the ground).
0
Disable
1
Enable
Menu
PAR
Description
15.24
4622
IOverC restart time
Setting of the time within which the Overcurrent [4] alarm must be reset in order to
perform automatic restart. (Time with alarm signal active + 1000 msec).
Menu
PAR
Description
15.25
4630
OverV restart
Enabling of automatic restart after the Overvoltage [1] alarm. This alarm indicates an
overvoltage on the intermediate circuit (DC link)
0
Disable
1
Enable
Menu
PAR
Description
15.26
4632
OverV restart time
Setting of the time within which the Overvoltage [1] alarm must be reset in order to
perform automatic restart. (Time with alarm signal active + 1000 msec).
Menu
PAR
Description
15.27
4640
UnderV restart
Enabling of automatic restart after the Undervoltage [2] alarm. This alarm indicates
an undervoltage on the intermediate circuit (DC link)
0
Disable
1
Enable
Menu
PAR
Description
15.28
4642
UnderV restart time
Setting of the time within which the Undervoltage [2] alarm must be reset in order to
perform automatic restart. (Time with alarm signal active + 100 msec).
126
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ms
UINT16
AFE200 • Instruction Manual
Def
Min
2000
1000
Def
Min
Disable
0
Def
Min
2000
1000
Def
Min
Disable
0
Def
Min
2000
1000
Def
Min
Enable
0
Def
Min
1000
120
Max
Acc
10000 ERW
Max
Acc
1
ERW
Max
Acc
10000 ERW
Max
Acc
1
ERW
Max
Acc
10000 ERW
Max
Acc
1
ERW
Max
Acc
10000 ERW

Advertisement

Table of Contents
loading