gefran AFE200 Series Instruction Manual page 80

Active front end regenerative power supply unit
Table of Contents

Advertisement

Example 2
With the machine controlled from console A, the drive operates in Local -> Terminal -> Standard digital
input mode.
With the machine controlled from console B, the drive operates in Remote ->Digital -> Expansion
digital input mode.
When switching the control console, the drive must switch between Remote and Local mode. The
switch command must be sent via Standard digital input or Expansion digital input.
This configuration is allowed because the Terminal variables are available in the digital command
selection lists.
Menu
PAR
Description
6.1
1000
Commands remote sel
This parameter defines the source of the command signals when the drive is used in
the Remote mode.
The Enable command can only be set via hardware, connecting a positive voltage
(+24VDC) to terminal 7.
0
Terminal
1
Digital
When the parameter is set to Terminals the source of the Enable cmd mon com-
mand is the Enable terminal (7)
When the parameter is set to Digital the origin of the Enable cmd mon command is
configured using the PAR 1018 Digital Enable src parameter.
If Digital is set to generate the Enable cmd mon command, as well as the variable
associated with Digital Enable src, the enable hardware command must also be sent
to the Enable terminal.
Menu
PAR
Description
6.2
1002
Commands local sel
This parameter defines the source of the command signals when the drive is used in
the Local mode.
0
Terminal
2
Keypad
When the parameter is set to Terminal the source of the Enable cmd mon command
is the Enable terminal (7) and the origin of the Start cmd mon command is config-
ured using the Terminal Start src parameter.
When the parameter is set to Keypad the origin of the Enable cmd mon is the Start
key. When Keypad is set to generate the Enable cmd mon command, as well as the
Start key the enable hardware command must also be sent to the Enable terminal (7)
Menu
PAR
Description
6.3
1008
Stop key mode
Setting of the Stop key functioning on the keypad in case of Remote->Terminal or
Remote->Digital or Local->Terminal mode. In Local -> Keypad mode this configuration
is ineffective.
80
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
UM
Type
FB BIT
ENUM
AFE200 • Instruction Manual
Def
Min
Terminal
0
Def
Min
Keypad
0
Def
Min
Inactive
0
Max
Acc
1
RWZ
Max
Acc
1
ERWZ
Max
Acc
1
ERW

Advertisement

Table of Contents
loading

Table of Contents