PAR
Description
13.2.3
3304
Par set select mon
The parameter set currently in use is displayed.
0
Set 0
1
Set 1
Menu
PAR
Description
13.2.4
3306
Par set 0 to 1 copy
Procedures for setting up and managing the double parameter set
Creating the second set:
This function copies parameter set 0 onto set 1. Before enabling management of the
double parameter set, the first set should be programmed with the correct values.
When the first set is ready, the second can be activated as follows:
1.
2.
3.
4.
5.
You can change the set being used by changing the source selected in parameter
3302 Par set select src. This can only be changed with the drive disabled.
When the double parameter set is active, the number of the set being used is shown
next to the number of each parameter on the keypad.
Modifying and saving parameters:
When the double parameter set is active, any parameters that need to be the same in
the two sets must be modified in each set separately.
Parameters are only saved in the set that is active at the time. To save both sets, you
must first save one and then select and save the other.
Note!
Any changes to the parameters regarding the "parameter sets", performed when enabled, will be lost
at the next switching unless a Par set 0 to 1 copy command is sent.
To save data permanently (even when the drive is switched off), send the Save pa-
rameters command (DRIVE CONFIG menu).
UM
UM
Activate management of the double parameter set by enabling parameter 3300
Par set enable.
Copy set 0 onto set 1 using command 3306 Par set 0 to 1 copy.
This creates an initial parameter base in set 1 to which changes can be made.
Save the parameters.
Activate set 1 using parameter 3302 Par set select src.
To select set 1 manually, set this parameter to "One".
Otherwise select the desired source.
Modify the parameters in set 1 as necessary.
Save the parameters.
Type
FB BIT
ENUM
16
Type
FB BIT
BIT
AFE200 • Instruction Manual
Def
Min
Set 0
0
Def
Min
0
0
Max
Acc
0
ER
Max
Acc
1
ERW
107