Bender COMTRAXX CP9 Series Manual page 39

Remote alarm indicator and operator panel for medical locations and other areas
Hide thumbs Also See for COMTRAXX CP9 Series:
Table of Contents

Advertisement

Visualisation
Number of pages .............................................................................................................................................................. 20
Background image size ..............................................................................max. 3 MB/image; max. 50 MB total memory
Interfaces
Ethernet
Connection.....................................................................................................................................................................RJ45
Data rate ....................................................................................................................................10/100 Mbit/s, autodetect
DHCP ................................................................................................................................................................on/off (off)*
T
(DHCP).................................................................................................................................................5...60 s (30 s)*
off
IP address................................................ nnn.nnn.nnn.nnn (192.168.0.254)*, can always be reached via: 169.254.0.1
Net mask........................................................................................................................ nnn.nnn.nnn.nnn (255.255.0.0)*
Protocols (depending on function module selected) ........................................ TCP/IP, Modbus RTU, DHCP, SMTP, NTP
BCOM
Interface/protocol........................................................................................................................................Ethernet/BCOM
BCOM system name ...........................................................................................................................................(SYSTEM)*
BCOM subsystem address ..............................................................................................................................1...255 (1)*
BCOM device address .....................................................................................................................................1...255 (1)*
USB
Number............................................................................................................................................................................... 2
Operating mode .................................................................................................................... USB-2.0-Host (5 V, 500 mA)
Datarate .............................................................................................................................................................. 480 Mbit/s
Connection type...................................................................................................................................... USB 2 Standard-A
Modbus TCP
Interface/protocol ............................................................................................................................ Ethernet/Modbus TCP
Operating mode ..................................................................................Client for PEM and "third-party devices" assigned
Operating mode .................................................Server for access to process image and for Modbus control commands
SNMP
Versions .....................................................................................................................................................................1, 2c, 3
Devices supported ........................................................Queries to all devices (channels) possible (no trap functionality)
BMS bus
Interface/protocol.............................................................................................................................. RS-485/BMS internal
Operating mode .............................................................................................................................master/slave (master)*
Baud rate................................................................................................................................................................9.6 kbit/s
Cable length......................................................................................................................................................... < 1200 m
Cable: twisted pair, shielded, one end of shield connected to PE ............................recommended: J-Y(St)Y min. 2x0.8
Connection.......................................................................................................... "ABMS", "BBMS" (see plug-in terminal)
Terminating resistor ...........................................120 Ω (0.25 W), can be switched on internally (see plug-in terminal)
Device address.................................................................................................................................................. 1...99 (1)*
Modbus RTU
Interface/protocol.............................................................................................................................. RS-485/Modbus RTU
Operating mode ........................................................................................................................................................master
Baud rate ................................................................................................................................................. 9.6...57.6 kbit/s
Cable length......................................................................................................................................................... < 1200 m
Cable: twisted pair, shielded, one end of shield connected to PE ............................recommended: J-Y(St)Y min. 2x0.8
Connection.............................................................................................................. "AMB", "BMB" (see plug-in terminal)
Terminating resistor ...........................................120 Ω (0.25 W), can be switched on internally (see plug-in terminal)
Supported Modbus RTU slave addresses .............................................................................................................. 2...247
CP9xx_D00349_07_M_XXEN/01.2020