CP9xx alarm indicator and operator panels are integrated into the existing EDP structure like PCs. After con-
nection to the network and compatible Bender products, all system devices can be accessed from any PC using
a web browser. In this way, all important system information is directly available. Verified web browsers: Mi-
crosoft IE, Mozilla Firefox, Google Chrome
The possibility of integrating all technical equipment into a single panel creates a "technical monitoring centre"
in the respective room. Each panel is individually manufactured and tailored to the requirements of the user.

2.6 Software products used

CP9xx devices are equipped with the COMTRAXX® user interface. It is described separately in the "COMTRAXX"
manual.

2.7 BMS side of the CP9xx display an operator panel

The majority of Bender devices communicate via the internal BMS bus.
The CP9xx alarm indicator and operator panel can be operated as a master or as a slave.
The CP9xx alarm indicator and operator panel is to be operated as a master if
- Parameters are queried or changed
- Certain control commands are issued
Please note that not all BMS masters can surrender their master function!

2.8 Address configuration and termination

To ensure proper functioning of the CP9xx alarm indicator and operator panel, correct address assignment
and termination is of utmost importance.
Multiple assignment of addresses
The factory setting for the system name on all Bender BCOM devices is "SYS-
TEM". If several systems with the same system name are integrated into the sa-
me network, addresses are assigned twice. This leads to transmission errors.
Always enter a unique BCOM system name during initial configuration.

2.9 Certification

Only the CP907 is UL-certificated.