36/94
Siemens Building Technologies
HVAC Products
/ /
T
Rw
Generation of setpoint with weather-compensated control without room unit
*
Multiplier
s
Slope of heating curve
T
Room temperature setpoint
Rw
T
Flow temperature setpoint
Vw
T
Composite outside temperature
AM
H
Heating curve
11.4.3 Setpoint of room temperature-compensated control
The setpoint is generated based on the deviation of the actual room temperature from
the setpoint. In addition, the heating curve with a fixed outside temperature of 0 °C is
taken into consideration.
/ /
T
T
Rx
/
1
2
E
+10 K
I
-10 K
Generation of setpoint with room temperature-compensated control
*
Multiplier
E
Room authority
H
Heating curve
I
Integrator with limitation
L
Limiter
S
Heating curve slope
T
Room temperature setpoint
Rw
T
Room temperature
Rx
T
Flow temperature setpoint
Vw
11.4.4 Setpoint of weather-compensated control with room
temperature influence
Here, in addition to the outside temperature and the room temperature setpoint, the
heating curve and the room temperature influence act on the flow temperature setpoint.
Basic Documentation RVD110, RVD130
11 Function block Space heating
s
s
Operating line 5 = setting of heating curve slope
Operating line 69 = setting of heat gains
Operating line 71 = setting of parallel displacement of heating curve
Rw
s
+50 K
L
-50 K
Operating line 5 = setting of heating curve slope
Operating line 69 = setting of heat gains
Operating line 70 = setting of room temperature influence (gain factor)
Operating line 71 = setting of parallel displacement of heating curve
T
AM
H
T
Vw
0 °C
s
1
s
T
H
Vw
CE1P2381E
27.05.2004