Installing; Basic Safety Notes; Atex/Iecx Special Conditions For Use - Siemens SIMATIC ET 200SP Operating Instructions Manual

Technology module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Installing

3.1

Basic safety notes

Open equipment
The devices are "open equipment" according to the standard IEC 61010-2-201 or UL
61010-2-201 / CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with
regard to mechanical stability, flame retardation, stability, and protection against contact, the
following alternative types of installation are specified:
● Installation in a suitable cabinet.
● Installation in a suitable enclosure.
● Installation in a suitably equipped, enclosed control room.
3.1.1

ATEX/IECx special conditions for use

Incorrect installation
Risk of explosion in the hazardous area. For use in hazardous areas according to Class I,
Division 2 or Class I, Zone 2 or for use in the EU according to ATEX 2014/34/EU, observe the
following conditions:
● Install the device in a control cabinet or enclosure.
● The control cabinet or enclosure meets at least the requirements of IP54 according to IEC/
Note
You must not install the device on a wall in hazardous areas.
Transient overvoltages
Take measures to ensure that temporary transient overvoltages of more than 119 V do not
occur.
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA
WARNING
WARNING
EN 60079-7 and pollution degree 2 or better according to IEC/EN 60664-1.
WARNING
3
17