Switch-On Delay Limit 3 (Empty) (S) [Delaytimeforemptylimit]; Dr07 Interface Parameters; Assignment Di.0, Di.1, Di.2, Ci [Functiondi0 To Functiondi2] [Functionci] - Siemens SIMATIC ET 200SP Operating Instructions Manual

Technology module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter assignment/addressing

6.9 DR07 Interface parameters

6.8.3

Switch-on delay limit 3 (empty) (s) [delayTimeForEmptyLimit]

Switch-on delay limit 3 (empty) can be deliberately delayed by a delay time. This is helpful, for
example, if the weight is undershot at the moment of opening when the scale is being emptied,
which would cause Limit 3 to be fallen below already.
6.9
DR07 Interface parameters
6.9.1

Assignment DI.0, DI.1, DI.2, CI [functionDI0 to functionDI2] [functionCI]

Assign a command to each digital input (DI.0, DI.1, DI.2): → Commands (Page 112).
Use counter input CI optionally as a fourth digital input with its own reference potential.
Selection code
[functionDI0]
[functionDI1]
[functionDI2]
[functionCI]
0 (default)
1 ... 32759
32760
32761
32762
32763
32764
32765
32766
32767
32768
32769 ... 65527
65528
65529
65530
65531
65532
65533
65534
65535
72
Function
The input operates as highspeed counter.
Command codes 1 to 32759 according to section Commands
(Page 112). Triggered on transition from 0 → 1 at DI.x
Example for command code 1121 → selection code = 1121
Transition weighing step 0
Transition weighing step 1
Transition weighing step 2
Transition weighing step 3
Transition weighing step 4
Transition weighing step 5
Transition weighing step 6
Transition weighing step 7
No function assigned
Command codes 1 to 32759 (+32768) according to section Commands
(Page 112). Triggered on transition from 1 → 0 at DI.x
Example for command 1121 → selection code = 1121 + 32768 = 33889
Transition weighing step 0 (inverted)
Transition weighing step 1 (inverted)
Transition weighing step 2 (inverted)
Transition weighing step 3 (inverted)
Transition weighing step 4 (inverted)
Transition weighing step 5 (inverted)
Transition weighing step 6 (inverted)
Transition weighing step 7 (inverted)
Technology module TM SIWAREX WP351 HF
Operating Instructions, 01/2020, A5E47521010-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tm siwarex wp351 hf

Table of Contents