User Restart Monitored (Max Number = 16 With M1, 32 With M1S With Other Restart Operators); Macro Restart Manual (Max Number = 16 With M1, 32 With M1S With Other Restart Operators) - Reer MOSAIC M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
USER RESTART MONITORED
(max number = 16 with M1, 32 with M1S with other RESTART operators)
The USER RESTART MONITORED operator is used
to save the restart signal (coming from a RESTART
command device) according to the following truth
table.
Clear
Restart
1
X
X
X
0
0
0
Parameters
Clear enable: If selected, enables an input to reset the memorization.
Restart request: If selected, it enables an output that can be used to signal the possibility
of performing the Restart. The behaviour can be of type 1 or type 2 (type 2 only with M1S)
as represented in the truth table.
*This output uses a system timer
MACRO RESTART MANUAL
(max number = 16 with M1, 32 with M1S with other RESTART operators)
The MACRO RESTART MANUAL operator is used to combine a
logic gate chosen by the user with the Restart Manual
functional block ("USER RESTART MANUAL") in accordance with
the following truth table.
Clear
Restart Logic Out
1
X
0
0
Rising Edge
8540780 • 10/07/2020 • Rev.38
In
Q
X
0
0
0
1
Keep Memory
1
1
Input Logic Out
X
X
0
Restart Request Type 1
0
0
1
0
Output
X
0
0
0
1
Keep memory
1
1
Restart Request Type 2*
1
1
Blinking 1Hz
0
Restart Request
0
0
1
0
179