Unlike the DELAY operator, the DELAY LINE operator does not filter any interruptions
in the IN input which are shorter than the set time.
This operator is recommended when using delayed OSSD (the OSSD must be
programmed with RESTART MANUAL).

LONG DELAY LINE

This operator applies a delay to a signal by
set time when a falling edge is detected on
If In returns to 1(TRUE) before the end of the
negative impulse lasting approximately twice
the system response time and delayed by the
set time.
Parameters
Time: The delay can be set from 0.5 s to 54915 s.
Scale: The user can choose two different scales for the time T to be set.
0,5 s...3000 s, step 0,5 s
3005 s...54915 s, step 5 s
Unlike the DELAY operator, the LONG DELAY LINE operator does not filter out any
interruptions to the IN input that are shorter than the set time.
This operator is useful when using delayed OSSDs (the OSSD must be programmed
with MANUAL RESTART).
202
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
the
2
t
x
cycle
8540780 • 10/07/2020 • Rev.38