Single E-Gate (Safety Gate Device) - Reer MOSAIC M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Output test: This is used to select which test output signals are to be sent to the component
contacts. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by opening the mobile guard or safety gate to run a complete
function test and enable the output. This test is only requested at machine start-up (when
the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the external contacts.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in ms) between the switching of two different signals from the external
contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.

SINGLE E-GATE (safety gate device)

SINGLE E-GATE function block verifies a mobile
guard or safety gate device input status. If the
mobile guard or safety gate is open, the output
is 0 (FALSE). Otherwise the output is 1 (TRUE).
Parameters
Enable reset: If selected this enables the
request
to
reset
guard/safety gate is activated. Otherwise,
enabling of the output directly follows the input
conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double transition
from 0 to 1 and then back to 0 is verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used. Example
: Input 1 and Input 2 are used for the fuctional block, then Input 3 have to be used for
the Reset Input.
Output test: This is used to select which test output signals are to be sent to the component
contacts. This additional control permits detection and management of any short-circuits
8540780 • 10/07/2020 • Rev.38
each
time
the
mobile
t = 250ms
t1 > 250ms
t2 = 250ms
117