MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
STATUS (SIL 1/PL c output)
STATUS output (SIL 1/PL c output) makes it
possible to monitor any point on the diagram
by connecting it to the input.
The output Is set at 24Vdc if the input is 1
(TRUE), or it is set at 0Vdc if the input is 0
(FALSE).
The STATUS output reaches only the SIL 1/Pl c safety level.
FIELDBUS PROBE
FIELDBUS PROBEs collect the logical status of any point of
the MSD schematic where they are attached.
These information are then transmitted over the fieldbus
and are represented with 4 bytes (M1S) or 2 bytes (M1).
The user could choose the bit position of a particular
probe within the transmitted byte.
It is possible to insert a maximum of 32 probes with M1S
and MBx fw >= 2.0 and 16 with M1 or MBx
fw < 2.0.
(For more detailed information, consult the fieldbus manual on the MSD CD-ROM).
WARNING: the PROBE output is NOT a safety output.
8540780 • 10/07/2020 • Rev.38
111