MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Using single channels OSSD, to maintain Safety Integrity Level (SIL) "3" requirements the OSSD
outputs must be independent.
Common cause failures between OSSD outputs must be excluded by observing an appropriate
cable installation (i.e. separate cable paths).
2 single output type function blocks + 1 double output type function blocks
Here below you can find the explanation of the M1S, MI8O4, MO4L, MO4LHCS8 SINGLE-OSSD
configurations.
Manual Reset: If selected this enables the request to reset each time the input signal falls. Otherwise,
output enabling directly follows In input conditions.
8540780 • 10/07/2020 • Rev.38
Example of project
t = 250ms
5s > t1 > 250ms
t2 = 250ms
109