Mi8O4 (Figure 37) - Reer MOSAIC M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
MI8O4
(
Figure 37
MEANING
Internal fault
Compatibility error
OSSD output error
Error in
communication with
master
Error on other
slave or M1
Same type of slave
with same address
detected
Overload on OSSD /
OSSD load connected
to 24V
Short circuit or
overload detected on
status output
Figure 37 -
MI8O4
8540780 • 10/07/2020 • Rev.38
)
RUN
IN FAIL
EXT FAIL
GREEN
RED
RED
2 or 3
OFF
OFF
flashes
5
OFF
OFF
flashes
4
OFF
OFF
flashes
5
OFF
OFF
flashes
OFF
ON
OFF
5
5
OFF
flashes
flashes
ON
OFF
ON
ON
OFF
ON
LED
SEL0/1
IN1÷8
ORANGE
YELLOW
RED/GREEN/YELLOW
OFF
5 flashes
OFF
(only the LED corresponding
Shows the
to the output in FAIL mode)
physical
address of the
unit
OFF
OFF
OFF
Shows the
Red blinking (only LED
physical
Inputs
corresponding to the
address of the
State
unit
Shows the
physical
Inputs
address of the
State
unit
Table 67 - Troubleshooting MI8O4
OSSD1/4
STATUS1/4
YELLOW
• Return the unit to ReeR
Red
OFF
• Firmware version not
5
5
flashes
flashes
• Check OSSD1/2
4 flashes
OFF
• If the problem persists,
• Restart the system
• If the problem persists,
OFF
OFF
• Restart the system
OFF
OFF
• Check which unit is in
• Change the unit's
OFF
OFF
OUTPUT
• Verify OSSD connections
state
relative output)
OUTPUT
• Verify output status
blinking
state
REMEDY
to be repaired
compatible with M1,
return to ReeR for FW
upgrade.
connections
return the unit to ReeR
to be repaired
return the MI8O4 to
ReeR to be repaired
FAIL mode
NODE
address (see
SEL
)
connections
75