Enclosure; M1 Module - Reer MOSAIC M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Response time M1S (ms)
This response times depends on the following
parameters:
1) Number of Slave modules installed
2) Number of Operators
3) Number of OSSD outputs
For the right response time refer to the one
calculated by the DSD software (see Project report)
Failure Response time M1S (ms)
This parameter corresponds to the response time,
with the exception of MV modules with
Encoder/Proximity interface where is 2s
M1 / M1S -> module connection
Connection cable cross-section
Max length of connections
Operating temperature
Max surrounding air temperature
Storage temperature
Relative humidity
Max. altitude (above sea level)
T
= max filtering time from among those set on project inputs
Input_filter
(see "INPUTS" section").

Enclosure

Description
Enclosure material
Enclosure protection class
Terminal blocks protection class
Fastening
Dimensions (h x l x d)

M1 module

PFH d (IEC 61508:2010)
Rated voltage
Dissipated power
Unit enable (No./description)
Digital INPUTS (No./description)
INPUT FBK/RESTART (No./description)
Test OUTPUT (No./description)
SIL 1/PL c OUTPUTS (No./description)
OSSD (No./description)
SLOT for MCM card
Connection to PC
Connection to slave units
8540780 • 10/07/2020 • Rev.38
Master
M1S + 1 Slave
M1S + 2 Slaves
M1S + 3 Slaves
M1S + 4 Slaves
M1S + 5 Slaves
M1S + 6 Slaves
M1S + 7 Slaves
M1S + 8 Slaves
M1S + 9 Slaves
M1S + 10 Slaves
M1S + 11 Slaves
M1S + 12 Slaves
M1S + 13 Slaves
M1S + 14 Slaves
ReeR proprietary 5-pole bus (MSC)
0,5 ÷ 2,5 mm
2
Electronic housing max 24 pole, with locking latch mounting
Quick coupling to rail according to EN 60715
108 x 22.5 x 114.5
24VDC  20%
2 / PNP active high "type B" according to EN 61131-2
8 / PNP active high according to EN 61131-2
2 / EDM control / possible Automatic
or Manual operation with RESTART button
4 / to check for short-circuits - overloads
2 / programmable - PNP active high
2 pairs / solid state safety outputs PNP active high
400mA@24VDC max - Interface type C class 3 (ZVEI CB24I)
USB 2.0 (Hi Speed) - Max cable length: 3m
via MSC 5-way ReeR proprietary bus
12,75 ÷ 14,75 + T Input_filter
13,83 ÷ 37,84 + T Input_filter
14,91 ÷ 40,00 + T Input_filter
15,99 ÷ 42,16 + T Input_filter
17,07 ÷ 44,32 + T Input_filter
18,15 ÷ 46,48 + T Input_filter
19,23 ÷ 48,64 + T Input_filter
20,31 ÷ 50,80 + T Input_filter
21,39 ÷ 52,96 + T Input_filter
22,47 ÷ 55,12 + T Input_filter
23,55 ÷ 57,28 + T Input_filter
24,63 ÷ 59,44 + T Input_filter
25,71 ÷ 61,60 + T Input_filter
26,79 ÷ 63,76 + T Input_filter
27,87 ÷ 65,92 + T Input_filter
/ AWG 12÷30 (solid/stranded)
100m
-10 ÷ 55°C
55°C (UL)
-20 ÷ 85°C
10% ÷ 95%
2000 m
Polyamide
IP 20
IP 2X
6.86E-9
3W max
Available
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mosaic m1s