Configuration with 2 dual channel
outputs (safety category SIL3/Pl e)

OSSD OUTPUTS CONFIGURATION

Each OSSD output can be configured as shown in Table 25:
The output is activated according to le configurations set by the MSD SW only if the
Automatic
corresponding RESTART_FBK input is conected to 24VDC.
The output is activated according to le configurations set by the MSD SW only if
Manual
corresponding RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF 0-->1.
The output is activated according to le configurations set by the MSD SW only if the
Monitored
corresponding RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF 0-->1-->0.
It is not allowed the connection of external devices to the outputs, except as expected
in the configuration performed with the MSD software.
42
t = 250ms
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Configuration with 4 single outputs
(safety category SIL3/Pl e)
Table 25
250ms < t1< 5s
t2 = 250ms
Figure 10
8540780 • 10/07/2020 • Rev.38