Free Configuration Of Digital Outputs - Lenze 9300 Series System Manual

Vector
Hide thumbs Also See for 9300 Series:
Table of Contents

Advertisement

6.5.2

Free configuration of digital outputs

Description
Codes for parameter setting
Code
Possible settings
No.
Name
Lenze Selection
C0117
s
1 CFG: DIGOUT1
15000 DCTRL−TRIP
2 CFG: DIGOUT2
10650 CMP1−OUT
3 CFG: DIGOUT3
500
4 CFG: DIGOUT4
5003 MCTRL−MMAX
C0118
1 DIGOUT1 pol
1
2 DIGOUT2 pol
1
3 DIGOUT3 pol
0
4 DIGOUT4 pol
0
Linking signals
Signal level
Inverting the signal level
EDSVF9383V EN 7.1−04/2012
Changing the assignment of the control terminals X5 and X6
ƒ The digital outputs X5/A1 ... X5/A4 can be freely linked with internal
digital signals.
ƒ One signal source can be linked with several targets.
^ Selection list 2
DCTRL−RDY
0
High active
HIGH level is
active
1
LOW active
LOW level is active
The digital outputs can be linked with internal digital signals by entering the
selection figure of the internal signal into corresponding subcode of C0117.
Example
ƒ C0117/2 = 505 ð signal source for X5/A2 is the status message
"direction of rotation" (DCTRL−CW/CCW)
ƒ Terminals (X5/A1 ... X5/A4):
– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V
ƒ Response times: 1 ms
In C0118 you can define the active signal level (HIGH level active or LOW level
active) for the terminals X5/A1 ... X5/A4.
Example
ƒ C0118/2 =1 ð With LOW level at X5/A2 the motor rotates in CW
direction (with in−phase motor connection)
l
Free configuration of digital outputs
IMPORTANT
Configuration of digital inputs
signals, function block DIGOUT
A change of the basic
configuration in C0005 changes
the signal assignment!
Terminal X5/A1
Terminal X5/A2
Terminal X5/A3
Terminal X5/A4
Inversion of digital output signals,
function block DIGOUT
Terminal X5/A1
Terminal X5/A2
Terminal X5/A3
Terminal X5/A4
6.5
6.5.2
^
6.5−3
See System
Manual
(extension)
6.5−3