6.3.2

Commissioning example in vector control mode

Switch−on sequence
1.
Insert the keypad
2.
Ensure that the controller is inhibited after
switching on the mains
3.
Ensure that no external error is active
4.
Switch on
A
The control card is supplied via an external voltage:
Switch on the external DC 24 V supply voltage
B
The control card is supplied via the internal voltage:
Switch on the mains. The controller provides the
DC 24 V supply.
5.
After approx. 2 s the controller is initialised and the
keypad is in the operating level and displays the
current speed (C0051)
6.
Change to the "Terminal I/O" menu and configure
the function of the control terminals to adapt them
to your application.
Lenze setting: C0005 = 1000 (basic configuration
"speed control")
7.
For quick commissioning select the menu "Short
setup"
Use V to change to the menu level
A
Use z z Z z to change to the menu "Short setup"
B
and then to the submenu "Setup vector"
Use Z to change to the code level to parameterise
C
your drive
8.
Adapt the controller to the mains (C0173)
Lenze setting: 1 (400 V mains voltage)
9.
Only for the variants V060, V110, V270, V300 in the
power range of 110 ... 400 kW:
Adapt the brake transistor threshold (C0174)
Lenze setting: 3 (500 V mains voltage, 885 V brake
voltage)
10.
Enter the motor data
A
If you use a Lenze motor:
Select the motor type connected under C0086.
B
If you do not use a Lenze motor:
Enter the data of the motor nameplate
l
Rated motor power (C0081)
– Lenze setting: device−dependent
l
Rated motor speed (C0087)
– Lenze setting: device−dependent
EDSVF9383V EN 7.1−04/2012
Parameter setting with the XT EMZ9371BC keypad
Commissioning example in vector control mode
The example describes how to commission a speed control for the controller
with power−related three−phase asynchronous motor.
z
Y Z
y
l
Note
}
Terminal X5/28 = LOW
X5
59
28
(see chapter "Commissioning"
®"controller inhibit")
misc008
Terminal X5/E4 = HIGH
ON
misc002
d
c
b
B
A
0050
00
0.00 Hz
0 %
9371BC004
Use C0002 = 0 to restore the Lenze
setting
(see chapter "Commissioning"
®"Change assignment of the control
terminal X5 and X6")
The submenu "Setup vector" contains
the codes that are required for
d
c
b
B
A
p
commissioning a standard application.
SHPRG
Menu
4
2
Code
Para
The digital inputs are configured in the
Quick start
Lenze setting:
V / f q u i c k
X5/E1: Deactivate CW rotation/quick
9371BC007
stop
X5/E2: Deactivate CCW rotation/quick
stop
X5/E3: Activate fixed setpoint 1 (JOG1)
d
c
b
B
A
X5/E4: Set error message (TRIP SET)
p
Menu
SHPRG
0034
00
Code
Para
0
X5/E5: Reset error message (TRIP
A I N 1 r a n g e
RESET)
9371BC008
(see chapter "Parameter setting")
See code table
See motor nameplate and chapter
"Commissioning" ® "Adapt motor
data"
The data of the Lenze motors are saved
under C0086.
6.3
6.3.2
6.3−5