Detecting And Eliminating Emc Interferences - Lenze 9300 Series System Manual

Vector
Hide thumbs Also See for 9300 Series:
Table of Contents

Advertisement

5.3
Basics for wiring according to EMC
5.3.7

Detecting and eliminating EMC interferences

5.3.7
Detecting and eliminating EMC interferences
5.3−6
Fault
Cause
Interferences of
Unshielded motor cable
analog setpoints of
Shield contact is not extensive
your own or other
enough
devices and
Shield of the motor cable is
measuring systems
interrupted by terminal strips,
switched, etc.
Install additional unshielded
cables inside the motor cable (e.g.
for motor temperature
monitoring)
Too long and unshielded cable
ends of the motor cable
Conducted
Terminal strips for the motor
interference level is
cable are directly located next to
exceeded on the
the mains terminals
supply side
Mounting plate varnished
HF short circuit
l
Remedy
Use shielded motor cable
Carry out optimal shielding as
specified
l
Separate components from
other component part with a
minimum distance of 100 mm
l
Use motor choke/motor filter
Install and shield additional cables
separately
Shorten unshielded cable ends to
maximally 40 mm
Spatially separate the terminal
strips for the motor cable from
main terminals and other control
terminals with a minimum
distance of 100 mm
Optimise PE connection:
l
Remove varnish
l
Use zinc−coated mounting
plate
Check cable routing
EDSVF9383V EN 7.1−04/2012