6.7

Setting the speed feedback

Description
Codes for parameter setting
Code
Possible settings
No.
Name
Lenze Selection
C0025
Feedback type
1
s
EDSVF9383V EN 7.1−04/2012
For speed monitoring, the feedback signal via incremental encoder can
either be supplied via input X8 or X9.
ƒ At input X8 you can only attach an incremental encoder with
TTL−levels.
ƒ Incremental encoders with HTL−level can only be connected to input
X9.
The incremental encoder signal can be output for slaves at the digital
frequency output X10.
The master frequency input (DFIN) and master frequency output (DFOUT)
are described in the chapter "Function library".
)
Note!
You can use maximally two of the three interfaces X8, X9, X10 at
the same time. This may lead to the fact that the incremental
encoder input cannot be activated or the master frequency input
or master frequency output does not work.
This does not apply if the input signal at X8 or X9 is directly
ƒ
output to master frequency output X10 (C0540 = 4 or 5).
To deactivate the master frequency input, the internal signal
ƒ
connection of function block DFIN to the following function
block must be removed. Remove the function block DFIN from
the processing table.
1
no feedback
No feedback
100
IT (C420) − X8
Input of the
number of
increments in
C0420
101
IT (C420) − X9
Input of the
number of
increments in
C0420
Number of
increments:
110
IT512−5V
512 inc
111
IT1024−5V
1024 inc
112
IT2048−5V
2048 inc
113
IT4096−5V
4096 inc
l
Setting the speed feedback
IMPORTANT
Speed feedback
Incremental encoder at X8
l
Incremental encoders with TTL
level can only be connected to
X8.
Incremental encoder at X9
l
Connect incremental encoders
with HTL−level on X9 only
Incremental encoder at X8
l
Incremental encoders with TTL
level can only be connected to
X8.
6.7
^
6.7−1
6.7−1