5.11.1
Functions on level
Submenu
CONFIGURATION
(c)
Functions as displayed
### ZONES defined / selected zone: ###
(c.3)
1. SET 1st zone number
2. ADD zones
3. DELETE zones
4. SELECT zone
5. CONFIGURE zones
(submenu of option '5.')
zone ### has ## elements
1. type ######
2. test
######
4. outputs (menu)
Option '1.'
Zone type
detector
DCin
X (4)
DIRECT
X (4)
LOCAL
MANUAL
X (4)
MULTI
X (4)
MULTI−LOC
X (4)
MULTI−2
X
MLT−2−LOC
TECHNICAL
TCH.SLF−H
TECHN.
SPRNK.LOC
EXT.REL
− to reserve a detector zone number for
BLANK
future use or
− for temporary shut−down of a zone
(1) Only if under 'line type' parameter '1.' is programmed
(2) Only if under 'line type' parameter '1.' and '2.' is progammed
(3) Only if 'CAC' is programmed either as option '1. ' or '3.' or '4. '
(4) State 'alarm' with OP(DO) and OH(DOT) can be intiated either with 'standard sensitivity' or with 'increased sensitivity' (see level 'DEVICE / field '3.')
(5) With prewarning the alarm indicator at the detector is flashing as long as state 'prewarning' is reported. If state 'prewarning' is continously reported
for > 5min then fault is initiated
Building Technologies
Fire Safety & Security Products
4. addressable line
1. line
2. device
3. zone
4. element
5. line 'collective'
6. CHECK configuration
7. CLEAR configuration
8. AUTOM. configuration
9. CONFIG ConTrol−ZONES
3. dsab
######
Application
DC1192
call point
coll.
X
X
X (3)
X
X
X
X
X
X
X (3)
X
X
X
X
X
X
X
X
X (3)
X
X
X
3. zone
ê
to define line type, number of devices, link devices
ê
to define device parameters
ê
to define zone parameters
ê
to define element parameters
ê
to link conventional lines to zone (if available)
ê
to check configuration before exit the programming mode
ê
to delete all user data
ê
to read actual line configuration as installed
ê
to define control outputs
Selectable options/Remarks
− to define where the zone numbering has to start (OFFSET)
– only to be changed if the zones do not have to start with number 1
– to add new zones
– to delete existing zones
– to select a specific zone number
− to define zone type and control allocation
− enter '1...4. ok' to open selection box
1. to define zone type
2. to define detector test allowed yes/no
3. to define disabling allowed yes/no
4. to allocate control outputs
Õ details see next page
Function
coll. line
⇒ state 'alarm'
X
⇒ state 'alarm'
X (1)
⇒ state 'alarm'
X (2)
⇒ re−alarm immediately after reset
⇒ state 'alarm' of 1 detector
⇒ state 'alarm' of 2 detectors simultaneously = alarm 2
⇒ state 'alarm' of 1 detector
⇒ state 'alarm' of 2 detectors simultaneously = alarm 1
⇒ state 'alarm' of 1 detector
⇒ state 'alarm' of 2 detectors simultaneously = alarm 2
⇒ state 'alarm' of 1 detector
⇒ state 'alarm' of 2 detectors simultaneously = alarm 1
⇒ state 'active'
(such a message must be erased after device is inactive)
⇒ state 'active'
(such a message disappears by itself after device is inactive)
⇒ state 'active'
⇒ state 'active'
⇒ state 'active' (extinguishing released)
− Such a zone has no function and no devices allocated.
− If an existing zone is changed to zone type BLANK all linked
devices will be unlinked.
= alarm 2
= alarm 1
= alarm 2
= fault 'broken glass'
= pre-alarm (5)
= pre-alarm (5)
= alarm 0
(without CAC)
= alarm 0
(without CAC)
= message 'element STATUS'
= message 'element STATUS'
= alarm 2
= alarm 1
= alarm 2
83
1583_o_en_−−_5
08.2005