Siemens Synova FC330A Manual page 120

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

6.10
Serial port application BMS
FC330A-> 3
detector zone ALARM with element address
remote ALARM
conTrol zone state ACTIVE / INACTIVE
general FAULT
mains FAULT
battery FAULT
detector zone FAULT with element address
remote FAULT
input 1−4 state ACTIVE as configured
detector zone DISABLED / ENABLED
conTrol zone DISABLED / ENABLED
detector zone TEST / CANCELLED (single)
detector zone TEST / CANCELLED (range)
detector zone TEST−ALARM with element address
system ACK
system RESET
system on mode MANNED / UNMANNED
OFFSET information
116
Building Technologies
Fire Safety & Security Products
Open interface to 3
− building management system (BMS)
− driver module for mimic display panels for false floor etc. where element information
is required
Point-to-point connection
Monitored or non-monitored
Two way communication or restricted from FC330A to 3
Allows remote control of all important functions
User configuration and user texts are not transmitted
For protocol description consult local Alarmcom sales organization
or
Special TEST software
for remote control
rd
party system
For test purposes there is a software programm available that allows to operate the
FC330A remotely from a PC using the application BMS (on request available via hotline)
rd
party systems
RS232
SWE330A
rd
3
set detector zone to DISABLED / ENABLED
set conTrol zone to DISABLED / ENABLED
set detector zone to TEST / CANCEL (single)
ACK system
RESET system
set system to MANNED / UNMANNED
request OFFSET information
request SATUS
rd
party systems only
Third party
system
Additional info
user text and standard text
for events also for event
memory and alarm counter
party system -> FC330A
1583_o_en_−−_6
08.2005